D06F Pressure Reducing Valve
Spec Sheet: D06F Pressure Reducing Valve
D06F Pressure Reducing Valve – Balanced-Seat PRV with Set-Point Scale
The D06F is a balanced-seat pressure reducing valve that protects installations against excessive supply pressure and maintains a constant outlet pressure even under wide inlet pressure fluctuation.
Description
D06F Pressure Reducing Valve – Balanced-Seat PRV with Set-Point Scale
Features:
• Inlet pressure balancing – fluctuating inlet pressure has no effect on outlet pressure
• Outlet pressure set by adjustment knob with direct reading on the set-point scale
• Fully exchangeable high-quality synthetic valve insert
• Integral fine filter with 0.16 mm stainless steel mesh
• Adjustment spring isolated from the drinking water
• Dezincification-resistant brass housing with gauge connections on both sides
• Conforms to BS EN 1567; DVGW, WRAS and ACS approved
General Application:
Protects household, commercial and industrial water installations against excessive supply pressure, reducing pressurisation damage, water consumption and flow noise.
Specifications
| Size Range | 1/2” to 2” (DN15 to DN50) |
|---|---|
| Pressure Ratings | Max inlet 25 bar (brass filter bowl) / 16 bar (clear bowl); outlet 1.5–6 bar (preset 3 bar); min pressure drop 1 bar |
| Working Temperature | Max 70°C (10 bar / brass bowl); 30°C per EN 1567 |
| Suitable Media | Drinking water |
| End Connection | Threaded male connections (brass) |
| Materials | Dezincification-resistant brass housing, synthetic valve insert, EPDM diaphragm & seals, stainless steel filter |
| Approvals | DVGW, WRAS (up to 23°C), ACS; conforms to BS EN 1567 |
| Note | Use the SM06T brass filter bowl if the valve can be exposed to UV radiation or solvent vapours |